Big gold water cooler
How do we deal with a malfunction



How do we deal with the failure of the great goldwater refrigerator in changzhou
If none of the above works, contact my company's customer service. Please describe the type of machineFault codeAnd so that our staff can quickly judge the point of failure, and faster and better to solve the problem. Any questions about the equipment can be discussed with us. Your call is welcome。
Advice telephone:
After the sale of the golden refrigerator, the frequent failure of the golden refrigerator, the professional maintenance of the golden refrigerator, japan, the supply of the original spare parts for the oil refrigeration, the repair of the hubble refrigerator, the consultation of after the sale of the product, after the sale of the halber refrigerator agent, the free failure counselling
The reason for the gold-oil chiller to alert eh is that the pumped current relay action or the internal heat relay action of the blender
Application type: akz**8 (series) akzj**8 (series)
2. Anomalous detection method: akz**8 is detected by a pump exhaust relay (f1m). Akzj**8 is tested by a mixer internal heat relay.
Possible cause: akz - wrong oil pump line, poor fuel pipelines for users, failure of pumps, inappropriate viscosity in the use of oil
Akzj -- the mixer was wrong first, the mixer failed
4. Treatment measures according to different circumstances: removal of alien entanglements on fans replacement of mixer electric power, adjustment of power voltage until normal replacement of oils with a viscousity below vg32, improvement of ducts, replacement of pumps
The large-gold oil cooler control panel shows that a6 straight-flowing fans stopped turning their fans at less than 10rpm
Applicable type: akz148 akz328 akz438 akzj188 akzj358 akzj458
2. Anomalous detection method: velocity detection through horic inside the fan power
3. Unusual determination condition: rotation speed below 10rpm
Possible cause: connector failure, main plate bad fan power failure, power surge, power noise
5. Diagnosis of failure: whether the fan rotates the connection is normal the fan is able to turn light or not the led lamp on the panel of the electric generator is normal and changes the fan or the main p-board are judged to be normal。
6. How to deal with the failure of the changzhou great goldwater refrigerator
Large-gold oil cooler control panel shows u2 power voltage abnormal
1. Applicable type: akz**8 akzj**8 (series)
2. Anomalous detection method: detection by the current voltage of the power source of the mutator
Anomalous determination condition: 1. An instantaneous power outage
Possible cause: insufficient power voltage
Diagnosis of failure: whether the power voltage determines the direct current voltage on the main plate at 90% of the rated voltage*v (i. E. - adjusting the power voltage) or not